• eYc GS43/44 CO2 Transmitter Indoor / Duct Type

eYc GS43/44 CO2 Transmitter Indoor / Duct Type

Features : Measuring up to 10000 PPM.Voltage or current output and optional RS-485, and display.Free software configuration
Input : NDIR sensor
Output : 4 ... 20mA / 0 ... 20mA / 0 ... 10V / 0 ... 5V / 0 ... 1V
linear accuracy ( at +25 °C ) :
400 ... 2000 PPM:± 40 ppm ± 3 % of reading /
other : ± 50 PPM ± 3 % of reading
measuring range : 2000 / 5000 / 10000 PPM
Display : Optional
●Additional option (ILAC/TAF) Test report - Standard Calibration laboratory(Leb number: 3032)
Model : eYc-GS43GS44

Sensor type : NDIR sensor
CO2 measuring range : 0 ... 10000 PPM
Signal connection : 3-wire
Load resistance :
Voltage output:≧ 10K Ω 
Current output:< 250 Ω
Response time : GS43: < 2 min. ; GS44 : < 6 min.
Power supply : DC 12 ... 36 V & AC 24 V ± 10 %
Protection rating : GS43 : IP54 ;GS44 : IP64

Accessory table
 Optional
  AS-HS-S
 Fixed board for wall type

  8203104014
 L Board fixed board for wall type

  M12-F4N-200
 Cable, M12 Waterproof, 4 PIN female, Length : 2M