• eYc FTM06C-A

eYc FTM06C-A Thermal Mass Air Velocity and Air Volume Transmitter

Output:4 ... 20 mA & RS-485 / 0 ... 10 V & RS-485 / RS-485 & Impulse (1 ... 500 Hz)
Input:Pt20/Pt300 (Air velocity) / Pt1000 (Temp.)
Measuring range:0 ... 5 m/s ~ 0 ... 60 m/s
Accuracy:±1.5% (Option±1%)
IP rating:IP65
Model : eYc FTM06C-A

● Thermal mass flow, quickly response, good sensitivity
● Turndown ratio 500:1, high precision & accurate sensing at lowest flow rate for metering applications
● Display Cumulative flow / Instantaneous flow
● Output:Analog / RS-485
● Use measured with square pipe or 2" pipe above
● IP rating:IP65
● Stainless steel casing, suitable for various severe environments, such as slightly corrosive air
Input
Input type:Pt20/Pt300 (Air velocity) / Pt1000 (Temp.)
Measuring range:0 ... 5 m/s ~ 0 ... 60 m/s
Min. measuring range:0.1 m/s
Turndown ratio:500:1
Installation angle effect:<3% of the measured value(When the installation angle<10°)

Output
Output:4 ... 20 mA & RS-485 / 0 ... 10 V & RS-485 / RS-485 & Impulse (1 ... 500 Hz)
Preset output:Out1:Air velocity
Signal connection:3-wire
Warm-up time:<60 sec
Response time:t90<5 sec
Load resistance:Voltage output:≧100 KΩ / Current output:≦500 Ω

Accuracy
Accuracy:±1.5% F.S. (Option±1%)
Temp. influence:0.1% / °C
Repeatability:0.5%

Electrical
Power supply:DC 24 V±10%
Current consumption:<0.3 A
Electrical connections:M12 connector

Environmental
Measuring medium:Air
Operating Temp.(With body and display):0 ... +50°C
Operating Humid.(With body and display):20 ... 90%RH(Non-condensing)
Probe operating Temp.:0 ... +120°C(Increasing operating temperature will affect air velocity error)
Storage Temp.:-20 ... +60°C
Storage Humid.:0 ... 95%(Non-condensing)
Probe pressure:16 bar

Installation
Installation:Metal flange mount, R1/2" movable thread, Inline T type tube, Flange pipe

Certification
Certification:CE

Protection
IP rating:IP65
Electrical protection:■ Reverse polarity ■ Over-voltage ■ Short-circuit

Material
Cover:PC(Display) / SUS 304(No display)
Body (including probe):SUS304
Filter:SUS304
Weight:500 g(w / o cable)


*Please make sure the product and the device which connect with RS-485 are on common ground, avoid damaged product.


The specifications contained herein are subject to change without notice and any user of said specifications should verify from the manufacturer that the specifications are currently in effect.
Otherwise, the manufacturer assumes no responsibility for the use of specifications which may have been changed and are no longer in effect.


Compressed air monitoring / Exhaust gas emission flow monitoring / Special gas process / Semiconductor / Electronics factory / Industrial process air velocity and air volume measurement