Huba 520 IO-Link Pressure sensor
Medium: Liquids, gases and refrigerants (incl. ammonia)
Pressure range: -1 ... 9 bar / 0 ... 2.5 – 1000 bar
Output: IO-Link
Accuracy: <0.3%F.S.
Features
The pressure transmitter Type 520 for industrial applications impresses with its compact and robust design as well as high accuracy and reliability. The hermetically welded stainless steel sensor offers very high overpressure safety and is suitable for use in gases, liquids and all common refrigerants including ammonia.
Huba Control offers with the Type 520 a universally applicable pressure transmitter with IO-Link communication technology.
IO-Link is a standardized, digital point-to-point connection that allows the user to easily wire the unit and access a wide range of specific device and process data. IO-Link offers numerous possibilities for device diagnostics, allowing the status of the pressure transmitter to be continuously monitored.
This makes the 520 IO-Link the ideal pressure transmitter for your Industry 4.0 application.
• Compact, rugged construction
• Welded without sealing parts, no elastomer seals
• Communication via IO-Link 1.1 (Smart Sensor Profile ED2)
• Sensor diagnosis function
• High flexibility of process connections
Specification
| Product Features | |
|---|---|
| Pressure measuring range | Relative: -1 ... 9 bar |
| Accuracy | typ.; max. 0.5% FS |
| Temperature range | Medium: -40 ... +100°C |
| Overload | < 6 bar: 5 x FS |
| Response time | < 2 ms (typ.) |
| Electrical Data | |
| Output / Communication | 4 wire IO-Link |
| Power supply | 18 ... 33 VDC |
| Current consumption | < 15 mA (typ.) |
| Protection | Polarity reversal protection |
| Materials | |
| Housing | Stainless steel 1.4404 / AISI 316L |
| Pressure connection | Stainless steel 1.4404 / AISI 316L |
| Plug accommodation | Polyarylamide 50% GF UL 94 V-0 |
| Approvals | |
| EMC | EN 61326-2-3 CE |
| Shock | IEC 60068-2-27 100 g, 11 ms |
| Vibration | IEC 60068-2-6 20 g, 15 ... 2000 Hz |
| UL | ANSI/UL 61010-1 |
Applications
Solar heating / Refrigeration systems / CDU / In-Rack CDU / Circulation cooler / Large heat pumps / Water pumps / Water treatment / Mobile hydraulics / Industrial automation
Download
Note : Design and specifications are subject to change without notice.
Note : Please make sure the product and the device which connect with RS-485 are on common ground, avoid damaged product.