Huba 528 OEM type Pressure Transmitter
Medium : Liquids and gases
Pressure range : -1 ... 0 – 60 bar
Output : 0 ... 5 V, 1 ... 6 V, 0 ... 10 V, 4 ... 20 mA, ratiom. 10 ... 90%
Accuracy : typ. < 0.3% fs
Features
The compact type 528 pressure transmitter is based upon the well proven ceramic technology developed by Huba Control over 20 years ago. These transmitters are suitable for applications across a broad spectrum of industries.
• Compact, rugged construction
• Negligible temperature influence on accuracy
• Large selection of connections available
• Saving time by quick cable mounting by the customer with swift connector
Specification
| Product Features | |
|---|---|
| Pressure range | Relative: -1 ... 0 ... 60 bar |
| Accuracy | Characteristic line a: ± 0.3% fs |
| Operating Conditions | |
| Medium | Liquids and gases |
| Temperature | Medium: |
| Tolerable overload / Rupture pressure | < 4 bar: 3.0 x fs |
| Materials | |
| Cover | Stainless steel 1.4404 / AISI 316L |
| Plug accommodation | Polyarylamide 50% GF UL 94 V-0 |
| Materials in contact with medium | Pressure connection: Stainless steel 1.4404 / AISI 316L / PVDF |
| Electrical Data | |
| Output | 2 wire: 4 ... 20 mA (7 ... 33 VDC / 10 ... 30 VDC) |
| Load / Current consumption | Voltage outputs: > 10 kOhm / < 100 nF |
| Polarity reversal protection | Short circuit proof and protected against polarity reversal. |
| Insulation voltage | 500 VDC |
| Response time | < 2 ms (1 ms typ.) |
| Electrical connection | Swift connector (with or without cable 1.5 / 2.0 / 3.0 / 5.0 m) |
| Protection class | IP65 / IP67 depending on connection |
| Installation | |
| Installation arrangement | Unrestricted |
| Approvals | |
| EMC | CE conformity acc. EN 61326-2-3 |
| Shock | IEC 68-2-27 100 g, 11 ms half sine wave |
| Vibration | IEC 68-2-6 20 g, 15 ... 2000 Hz |
| UL | ANSI/UL 61010-1 acc. E325110 |
| Drinking water approval | NSF/ANSI 61 / 372 acc. MH60087 |
| Explosion protection | Ex II 1/2 G Ex ia IIC T4 Ga/Gb |
| Weight | ~ 90 g |
Applications
Solar heating / CDU / In-Rack CDU / Circulation cooler / Large heat pumps / Water pumps / Water treatment / Mobile hydraulics / Industrial automation
Download
Note : Design and specifications are subject to change without notice.
Note : Please make sure the product and the device which connect with RS-485 are on common ground, avoid damaged product.