e2=a'+b'vn |
e: |
Sensor voltage output(V) |
a': |
Zero output of constant temperature hot wire anemometer, can use CTA circuit as temperature compensation |
|
b': |
Sensitivity of the sensor, related to the operating temperature |
|
v: |
Fluid flow rate |
|
n: |
0.45 ... 0.5(Standard) |
Input |
|
Input type |
Pt20 / Pt300 (Air velocity) / Pt1000 (Temp.) |
Measuring range |
0 ... 120 Nm/s |
Minimum initial value |
0.15 Nm/s |
Installation angle effect |
<3% of the measured value (When the installation angle<10°) |
Output |
|
Signal |
4 ... 20 mA / 0 ... 10 V / RS-485 / Impulse |
Preset output |
Out1 : Air velocity;Out2 : Impulse |
Impulse range (1 ... 500 Hz) |
(1)1 ... 500 Hz : 4 ... 20 mA |
Signal connection |
3-wire |
Warm-up time |
<60 sec |
Reaction time |
t90<5 sec |
Display type |
LCD Module with back light, double-row |
Load resistance |
Current output : ≦500 Ω |
Accuracy |
|
Accuracy |
±1.5% F.S. (Option ±1%) |
Temp. influence |
0.1% / °C |
Repeatability |
0.5% |
Electrical |
|
Power supply |
DC 24 V±10% |
Current consumption |
<0.3 A |
Overvoltage protection |
DC : <40 V |
Electrical connections |
M12 connector / M16 metal cable gland |
Environmental |
|
Measuring medium |
Air |
Operating Temp. |
-20 ... +60°C |
Operating Humid. |
0 ... 95%RH(Non-condensing) |
Probe operating Temp. |
0 ... 120°C / Option:200°C |
Storage Temp. |
-20 ... +60°C |
Storage Humid. |
0 ... 95%RH(Non-condensing) |
Probe pressure |
16 bar |
Installation |
|
Fixed seat |
1/2″PT movable thread |
Installation |
Duct type / Remote type |
Protection |
|
IP rating |
IP67(Probe);IP65(Housing) |
Electrical protection |
■ Reverse polarity ■ Over-voltage ■ Short-circuit |
Certification |
|
Certification |
CE |
Material |
|
Housing |
Aluminum alloy |
Probe |
SS304 ( Option SUS316 ) |
Remote probe cable |
TEFLON (Remote FTM95) |
Weight |
FTM94 : 720 g / FTM95 : 832 g |