Measuring range:±300 ... ±10000 pa
Input:Piezoelectric differential pressure module
Output:4 ... 20 mA / 0 ... 10 V
Accuracy:±2.0% of F.S.
Display :Optional
Model : eYc PHD330

● Silicon chips on differential pressure module of MEMS integration technology
● Offset function / UI software
● Low-pressure monitoring, high pressure resistance
● RS-485 communication interface(Optional), Modbus RTU protocol
● Physical unit switch(User Interface):mbar / Pa / hPa / kPa / mmH2O / mmWS / inH2O / mmHg
● Square root function

More potential product articles, welcome to visit the link below

eYc-Success-StoryeYc-FAQ

Input type:Piezoelectric differential pressure module
Measuring range:±300 ... ±10000 pa
Output:4 ... 20 mA / 0 ... 10 V
Signal connection:3-wire
Modbus:RS-485
Measuring medium:Air
Operating temperature:-20 ... +80°C(Non-display) / 0 ... +50°C(Display)
Operating humidity:0 ... 95%(Non-condensing)
Storage temperature:-40 ... +80°C
Accuracy:±2.0% of F.S.
Power supply:AC 24 V ±10% / DC 24 V ±10%
Installation:Wall
IP rating:IP65
Housing:Aluminum alloy

*Please make sure the product and the device which connect with RS-485 are on common ground, avoid damaged product.

The specifications contained herein are subject to change without notice and any user of said specifications should verify from the manufacturer that the specifications are currently in effect.
Otherwise, the manufacturer assumes no responsibility for the use of specifications which may have been changed and are no longer in effect.


The eYc PHD330 differential pressure transmitter is designed on the MEMS hot wire anemometer architecture, which has very good zero point stability and small differential pressure detection capability, high pressure resistance. The transmitter uses the pressure difference to pass a very small amount of gas through the air flow channel of the sensor body. Combined with the integrated circuit to convert into a differential pressure signal.
Exhaust emission / Environmental engineering / Air duct / Filter / Monitor differential pressure and environment air flow