eyc-tech FDM06-X Thermal Mass Diff. Pressure Signal Processor

eyc-tech FDM06-X
High-accuracy thermal mass differential pressure sensor with K-factor correction, real-time display, versatile outputs, and compatibility with various elements.
  • eyc-tech FDM06-X Thermal Mass Diff. Pressure Signal Processor
Features
● Thermal mass differential pressure principle
High accuracy ±1.5% F.S., without the need for temperature or pressure compensation
● Turndown ratio 100:1 with high sensitivity design
Superior to conventional differential pressure sensors in detecting subtle airflow variations
● On-site K-factor correction
Simple calculation allows input of the corresponding K-factor to align measurements with true values
● Real-time display & system integration
Capable of showing flow velocity/flow rate, and with eyc-tech DPM03 / DPM04 enables full-range linearization and totalizing flow calculation
● Versatile outputs
Supports Analog / Relay / RS-485, making system integration flexible and convenient
● Easy installation
Ferrule fittings for flexible or rigid tubing.
● High compatibility
Applicable to a wide range of differential pressure elements (Pitot tube, averaging tube, Annubar, Venturi, orifice plate, V-cone, etc.)
Applications
Industrial compressed air & energy management:Zonal consumption monitoring, leakage detection, energy metering
Process gases & supply control:Flow billing, mixing ratio monitoring, high-pressure/high-velocity flow monitoring
HVAC & cleanroom:Duct flow monitoring, laminar flow, positive/negative pressure, environmental control
Biotech & pharmaceutical:Aseptic area and gas supply stability monitoring
Environmental monitoring & ESG:Emission measurement, CO2 equivalent conversion, ESG energy statistics
Applications
High-accuracy thermal mass differential pressure sensor with K-factor correction, real-time display, versatile outputs, and compatibility with various elements.
Specification

Input

Sensor type
Hot-wire sensor
Turndown ratio
100 : 1
Measuring range
Max. 60 m/s

Output

Output signal
4 ... 20 mA / 0 ... 10 V / Relay / RS-485
Signal connection
3-wire
Warm-up time
60 sec
Response time
t90≦6 sec
Load resistance
Current output : ≦500 Ω
Voltage output : ≧10 KΩ

Communication

Communication methods & protocol
RS-485 Modbus RTU
RS-485 baud rate
9600、19200、38400、57600、115200 bps

Accuracy

Accuracy
60 m/s:±(1.5% F.S.)
Temp. influence
0.2% / °C
Uncertainty of factory calibration
±1%
*The measurement range is defined at the standard condition(1013 mbar, 20°C).
*Accuracy based on tests with a 300 mm averaging Pitot tube.

Environmental

Medium
Non-corrosion gas / Air
Operating Temp.
0 ... 50°C / 20 ... 90%RH (Non-condensing)
Operating Humidity
20 ... 90%RH(Non-condensing)
Storage Temp.
-20 ... +60°C
Body operating pressure
16 bar

Electrical

Power supply
DC 24 V ±10%
Current consumption
24 V : 110 mA
Relay capacity
Max current : 6 A
Max voltage : DC 24 V (DC 36 V Max)
Electrical connection
M12 8P connector

Installation

Installation
Ferrule fittings:1/4″(Rigid), Ø6(Flexible)

Display

Display readout
0 ... 99999999 (Cumulative flow : 8-digit)
0 ... 99999 (Instantaneous flow : 5-digit)
Decimal point
Button
Sampling time
1 cycle/sec
Flow unit
m/s, ft/s, L/min, m³/min, m³/h, mL, L
m³, ft³, inch³, gal, uk gal
Response time adjustment range
0.5 ... 300 sec

Certification

Certification
CE

Protection

IP rating
IP65(Housing)
Electrical protection
■ Reverse polarity ■ Over-voltage

Material

Housing
Aluminum alloy

Note : Design and specifications are subject to change without notice.
Note : Please make sure the product and the device which connect with RS-485 are on common ground, avoid damaged product.