PR 6334A 2-wire Programmable Transmitter

PR 6334A
  • PR 6334A 2-wire Programmable Transmitter
Features
  • TC input
  • High measurement accuracy
  • Galvanic isolation
  • Programmable sensor error value
  • 1- or 2-channel version

    Application

  • Linearized temperature measurement with TC sensor.
  • Amplification of bipolar mV signals to a 4...20 mA signal, optionally linearized according to a defined linearization function.

    Technical characteristics

  • Within a few seconds the user can program PR6334A to measure temperatures within all TC ranges defined by the norms.
  • Cold junction compensation (CJC) with a built-in temperature sensor.
  • A limit can be programmed on the output signal.
  • Continuous check of vital stored data for safety reasons.

    Mounting / Installation

  • Mounted vertically or horizontally on a DIN rail. Using the 2-channel version up to 84 channels can be mounted per meter.
  • The 6334A can be mounted in zone 2 and zone 22.

    Please contact the sales for details.
Specification
Environmental Conditions
Operating temperature -40°C to +85°C
Storage temperature -40°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20

Mechanical specifications
Dimensions (HxWxD) 109 x 23.5 x 104 mm
Weight (1 / 2 channels) 145 / 185 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13...2.08 mm2 AWG 26...14 stranded wire
Screw terminal torque 0.5 Nm

Common specifications
Supply
Supply voltage 7.2...35 VDC
Max. required power ≤ 0.8 W/≤ 1.6 W (1 ch./2 ch.)
Internal power dissipation 0.17...0.8 W
Isolation voltage
Isolation voltage, test / working 1.5 kVAC / 50 VAC
Response time
Response time (programmable) 1...60 s
Voltage drop 7.2 VDC
Warm-up time 5 min.
Programming Loop Link
Signal / noise ratio Min. 60 dB
Accuracy Better than 0.05% of selected range
EEprom error check < 3.5 s
Signal dynamics, input 18 bit
Signal dynamics, output 16 bit
Effect of supply voltage change < 0.005% of span / VDC
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span

Input specifications
Common input specifications
Max. offset 50% of selected max. value
TC input
Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold junction compensation (CJC) < ±1.0°C
Voltage input
Measurement range -12...150 mV
Min. measurement range (span) 5 mV
Input resistance Nom. 10 MΩ

Output specifications
Current output
Signal range 4…20 mA
Min. signal range 16 mA
Load (@ current output) ≤ (Vsupply - 7.2) / 0.023 [Ω]
Sensor error indication Programmable 3.5…23 mA
NAMUR NE43 Upscale/Downscale 23 mA / 3.5 mA
Common output specifications
Updating time 440 ms
of span = of the presently selected range
Download
Note : Design and specifications are subject to change without notice.