Schmidt SS 20.250 Flow Sensor

Schmidt SS 20.250
  • Schmidt SS 20.250 Flow Sensor
Features
For ventilation, air-conditioning, cleanroom and pharmaceutical applications.

In many applications, direct measurement of the flow velocity and of the volumetric flow in air and gases is the ideal solution. Owing to the high requirements in modern control technology, the flow sensor used must be able to measure precisely and quickly over an extremely wide range from "almost zero" to the maximum value.

Typical applications of the SCHMIDT® Flow Sensor SS 20.250 with dumbbell head technology include:
Monitoring and energy-efficient controling of fans
Continuous monitoring of filter units
 Safe control of the volumetric flow of extraction units
 Monitoring of the laminar flow in cleanrooms
The smallest all-rounder

Thanks to its compact mechanical design, the SS 20.250 can be installed very easily via a flange or a compression fitting. Its complete electronics are housed in the robust metal sensor tube, which has a diameter of only 9 mm.

Technology
Thanks to the dumbbell technology used and the high flow angle (radial: 360°, axial: ± 45°), the sensor can be positioned in the gas flow safely and quickly. In addition to detecting the standard flow velocity of 0.06 to 20 m/s, it also measures the temperature of the medium. The available linear output signals are 4...20 mA and
0...10 V in each case – as a function of the connected load resistance giving you a universal sensor and automatic detection of U or I output.

Measuring accuracy in black and white
Optionally, the SCHMIDT® Flow Sensor SS 20.250 can also be delivered with high-precision calibration and ISO calibration certificate, which documents its high precision and reproducibility. You can have this calibration renewed at any time.

Protection from dust and aggressive gases
Using the patented dumbbell head also allows measurements to be made in dust-containing gases. If the sensor gets dirty, it can be cleaned again by the user without problems. Upon request the sensor can also be delivered two special protective coatings to increase the resistance against aggressive media such as hydrochloric acid, acetone, sulfuric acid and many more.

Accuracy in black and white
On request the SCHMIDT® flow sensor SS 20.250 can be delivered with an ISO calibration certificate which documents the high accuracy and reproducibility of flow measurement on the basis of real measuring values and deviations. SCHMIDT Technology carries out the measurement in reference channels. This calibration can be renewed by the user at any time.
Specification
Medium:Air or nitrogen, other gases upon request
Measuring range:0 ... 1 / 10 / 20 m/s / selectable
Output:4 ... 20 mA / 0 ... 10 V 
Operating temperature:-20 ... +70 °C
Accuracy:±(5% of measured value + [0.4% of final value; min. 0,02 m/s])
Operating pressure:Atmospheric (700 ... 1,300 hPa)
Ingress protection / protection class:IP 65 / III (SELV) or PELV
Download
Note : Design and specifications are subject to change without notice.
Note : Please make sure the product and the device which connect with RS-485 are on common ground, avoid damaged product.