Measurement
|
Measuring element
|
Thermal mass type
|
Input
|
Differential
|
Measuring range
|
±10, ±25, ±50, ±100 Pa
|
Output
|
Output
|
4 ... 20 mA / 0 ... 10 V / Relay / RS-485
|
Signal connection
|
M12, 3-wire
|
Warm-up time
|
60 sec
|
Response time
|
t90 ≦ 6 sec
|
Load resistance
|
Current output : ≦ 500 Ω
Voltage output : ≧10 KΩ
|
Communication
|
Communication methods & protocol
|
RS-485 Modbus RTU
|
RS-485 baud rate
|
9600, 19200, 38400, 57600, 115200 bps
|
Accuracy
|
Accuracy
|
±(1% F.S. + 0.1 Pa)
|
Temperature influence
|
±0.5% F.S./°C
|
Environmental
|
Measuring medium
|
Air
|
Operating Temp. & Humid.
|
0 ... 50°C / 20 ...90%RH(Non-condensing)
|
Storage Temp.
|
-25 ... +60°C
|
Operating pressure
|
16 bar
|
Electrical
|
Power supply
|
DC 24 V ±10%
|
Current consumption
|
24 V : 60 mA
|
Relay capacity
|
Max current : 6 A
Max voltage : DC 24 V (DC 36 V Max)
|
Electrical connection
|
M12 8 PIN connector
|
Installation
|
Installation
|
Compatible with Ø8 PVC
PTFE pneumatic tubing
|
Display
|
Display readout
|
Diff. pressure value with two decimal places
|
Decimal point
|
Button
|
Sampling time
|
1 cycle/sec
|
Diff. pressure unit
|
Pa, mbar, hPa, mmWS, inH2O, mmHg
|
Response time adjustment range
|
0.5 ... 300 sec
|
Certification
|
Certification
|
CE
|
Protection
|
IP rating
|
IP65(Housing)
|
Electrical protection
|
■ Over-voltage
■ Reverse polarity
|
Material
|
Housing
|
Aluminum alloy / Plastic
|
Weight
|
207 g
|